ASB
Analog Sounder Base (Aux Power) Bone
ASB, a Digital analog Sounder Base that is designed for use with Hochiki digital analog sensors ALG-V, ALK-V, ACA-V, AIE-EA, and ATG-EA. Each addressable base is to be connected to a Hochiki America Corporation DCP Signaling Line Circuit (SLC).
The ASB provides an audible alarm in the immediate vicinity. Typical applications are hotels, apartments, and hospitals.
UL Approved Fire Detection
Product code : ASB
Description
Main features:
- Programmable evacuation codes – Continuous, March, ANSI Temporal patterns
- Base learns the sensor address and assumes an upper range address (128-254)
- Up to 127 sensors and 127 ASBs can be used on one SLCl oop
- Can be alarmed or reset by zone or by individual address
- ASB SLC loop wire resistance = 50 ohms Max. (total SLC wire run length)
- Operating Voltage :17 ~ 41 VDC
- Sound Pressure Level at 10ft.: 85dB
- Max. Quantity Per Loop: 127
- UL Ambient Installation Temperature Range :32°F (0°C) ~ 100°F (38°C)
- Operating Temperature Range: 32°F (0°C) ~ 122°F (50°C)
- Dimensions (without sensor): 1.34”H x 5.94”D
- Weight: 0.455 lb