K1171

16 Channel I/O Interface card

The 16 Channel I/O Interface enhances the versatility of the alarm system by providing additional input and output capabilities to the Taktis Fire Alarm Control Panel. Inputs and outputs can be selected for up to 16 individual channels. All inputs and outputs are configured in the same way as devices connected to addressable loops of the panel. The 16 Channel I/O Interface can be configured to contribute or act upon cause and effect logic.
This module must be housed in a separately-listed enclosure connected to the panel by metal conduit located within the same room. Power must be provided by a power supply listed for fire alarm service.

Product code: K560

Description

Use Case Examples

The 16 Channel I/O Interface can be used to interface the Taktis panel to a NAC extender or Voice Evacuation system, by providing:

  • inputs to the Taktis panel for dry contact closures such as General Trouble, AC Power Trouble, or Battery Trouble from these devices.
  • outputs from the panel to control various NAC or Voice Evacuation outputs.

The 16 Channel I/O Interface can be used to interface the Taktis panel to a secondary panel or releasing panel, by providing:

  • inputs to the Taktis panel for dry contact closures such as Fire, Supervisory, and Trouble from these panels, and various stages of release from the releasing panel.
  • outputs from the panel to activate NAC outputs on these panels.